BUSOL CONDENSATE CONTROL
(CORROSION INHIBITOR for STEAM AND CONDESATE)



BUSOL CONDENSATE CONTROL is unique blended formulation of alkyl amine and alkanol amine to prevent CO2 corrosions in condensate return system.

Application

  • BUSOL CONDENSATE CONTROL for use in Boiler system with condensate pH below 8.0
  • BUSOL CONDENSATE CONTROL will reduce corrosion of condensate lines and, in doing si, will minimize cooper and iron pick up being returned to the boiler.


Direction for use
BUSOL CONDENSATE CONTROL may be fed as received or diluted to suitable strength with make up water continuously and proportionally into the feed water line by using injection pump.

Dosage

  • Dosage of BUSOL CONDENSATE CONTROL depends on M-alkalinity and acidity in condensate return.
  • Normally dosage rate between 5 – 40 ml per-tones of feed water.
  • Condensate pH should remain between 8.0-9.0.should pH vary from this range, adjust dosage rate of BUSOL CONDENSATE CONTROL.


Safety and Handling

  • Product contains alkaline organic amines, avoid contacts with skins or eyes. Avoid inhalation of vapors.
  • If contact with skin or eyes occur, wash with water for at least 20 minutes.
  • Use goggles ore face shield to avoid direct contact with BUSOL CONDENSATE CONTROL
  • Store in a cool and dry area.
  • Do not use empty containers for drinking water supply

 